ATV930C13N4 - frequency converter
new in sealed original packaging
Normal price
Price on request
/
- plus taxes + shipping
- Fast delivery
- New & Sealed Original Items
- Manufacturer's warranty on all parts
- Access to stock items available worldwide
- Feedback within 24 hours
- In stock
- Inventory on the way
Series | Altivar Process ATV900 |
---|---|
Device Application | Industrial application |
Product or component type | Variable speed drive |
Product determination | Synchronous motors Asynchronous motors |
Product-specific application | Process for industrial |
Variant | Standard version With brake chopper |
Number of network phases | 3 phases Single phase |
Assembly mode | Surface mounting |
Communication protocol | Ethernet IP/Modbus TCP Modbus |
Nominal operating voltage [U,nom] | 380-480 V -15 - +10% |
Motor power (kW) | 132.0 kW for normal operation 110.0 kW for heavy duty operation |
Output rated current | 250 A at 4 kHz for normal operation 211 A at 4 kHz for heavy duty operation |
EMC filter | Integrated With EMC plate option |
IP protection class | IP21 |
Protection class | UL Type 1 |
optional module | Slot A: Communication module for Profibus DP V1 Slot A: Communication module for Profinet Slot A: Communication module for DeviceNet Slot A: Communication module for EtherCAT Slot A: Communication module for CANopen Daisy Chain RJ45 Slot A: Communication module for CANopen SUB-D 9 Slot A: Communication module for CANopen screw terminals Slot A/Slot B/Slot C: Expansion module for digital and analog I/O Slot A/Slot B/Slot C: Expansion module for output relay Slot B: 5/12 V digital encoder interface module Slot B: Analog encoder interface module Slot B: Interface module for encoder with actual value feedback |
Type of motor control asynchronous motor | Constant torque Variable torque Optimized torque operating mode |
Control profile for synchronous motors | Permanent magnet motor Synchronous reluctance motor |
max.Output frequency | 599 Hz |
Clock frequency | 1 - 8 kHz adjustable 2.5 - 8 kHz with power derating factor |
Rated clock frequency | 2.5 kHz |
Mains power | 237.0 A at 380 V (normal operation) 201.0 A at 380 V (heavy duty operation) 213.0 A at 480 V (normal operation) 165.0 A at 480V (heavy duty operation) |
Apparent power | 161.4 kVA at 380-480 V (normal operation) 121.8 kVA at 380-480 V (heavy duty operation) |
maximum peak current | 300 A during 60 s (normal operation) 317 A during 60 s (heavy duty operation) |
Network frequency | 50 - 60 Hz |
Mains short-circuit current Ik | 50 kA |
Discrete input number | 10 |
---|---|
Output type of the relay | Configurable relay logic R1: fault relay normally open/closed electrical life 100,000 cycles Configurable relay logic R2: sequence relay normally open (S) electrical service life 1000,000 cycles Configurable relay logic R3: sequence relay normally open ( S) electrical lifespan 1000000 cycles |
Physical interface | Ethernet 2-wire RS 485 |
Connection type | 2 RJ45 1 RJ45 |
Access method | Slave Modbus TCP |
Transmission speed | 10, 100 Mbits 4.8 kbps 9,600 bit/s 19200 bit/s |
Transmission frame | RTU |
Number of addresses | 1…247 |
Data format | 8 bits, adjustable to odd, even or no parity |
Polarization type | No impedance |
4 quadrant operation possible | Correct |
High and deceleration ramps | Linear adjustable separately from 0.01-9999 s S, U or user defined |
Slip compensation motor | Adjustable Automatic, independent of load Can be deactivated Not available in permanent magnet motor control |
Brake to standstill | By direct current supply |
Brake chopper integrated | Correct |
Max.Input current | 237.0 A |
Maximum output voltage | 480.0V |
Relative symmetric network frequency tolerance | 5% |
Base load current at high overload | 211.0 A |
Base load current at low overload | 250.0 A |
with Safely Limited Speed (SLS) safety function | Correct |
with safety function Safe brake management (SBC/SBT) | Correct |
with safety function Safe Operating Stop (SOS) | False |
with Safe Position (SP) safety function | False |
with safety function Safe programmable logic | False |
with Safe Speed Monitor (SSM) safety function | False |
with safety function Safe Stop 1 (SS1) | Correct |
with safety function Safe Stop 2 (SS2) | False |
with safety function Safe torque off (STO) | Correct |
with Safely Limited Position (SLP) safety function | False |
with safety function Safe Direction (SDI) | False |
Protection functions | Thermal protection: motor Safe torque off: motor Motor phase failure: motor Thermal protection: drive Safe torque off: drive Overtemperature: drive Overcurrent protection between Output phases and ground: drive Output voltage overload: drive Short circuit protection: drive Motor phase failure: drive Overvoltage protection on the DC bus: drive Overvoltage protection supply voltage: drive Undervoltage detection mains voltage: drive Phase failure detection of the supply voltage: drive Overspeed: drive Interruption detection in the control circuit: drive |
Quantity per set | 1 |
Width | 320mm |
Height | 1205mm |
Depth | 393mm |
Product weight | 104kg |