X20DO9322 - Digital output module

X20DO9322 - Digital output module

new in sealed original packaging
Normal price 1.020,00 kr
/
  • plus taxes + shipping

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

  • Fast delivery
  • New & Sealed Original Items
  • Manufacturer's warranty on all parts
  • Access to stock items available worldwide
  • Feedback within 24 hours
  • In stock
  • Inventory on the way
  • American Express
  • Apple Pay
  • Google Pay
  • Klarna
  • Maestro
  • Mastercard
  • PayPal
  • SOFORT
  • Union Pay
  • Visa

Do you need more than what we have in stock? Just ask us.

DESCRIPTION:

  • 12 digital outputs
  • Source circuit
  • 1-wire technology
  • Integrated output protection

The module is equipped with 12 outputs in 1-wire technology. The outputs of the module are designed for source connection.

 

Short description

I/O module 12 digital outputs 24 VDC in 1-wire technology

General

B&R ID code 0x1B9A
Status displays I/O function per channel, operating status, module status
Diagnostics
Module Run/Error Yes, via status LED and SW status
Outputs Yes, via status LED and SW status (output error status)
Power consumption
Bus 0.26W
I/O internal 1.15W
Additional power loss due to actuators (resistive) [W]  +0.63
Approvals
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial Control Equipment
HazLoc cCSAus 244665
Process Control Equipment
for Hazardous Locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B(0 to 55 °C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck)
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55 °C
Vibration: 4 g
EMC: Bridge and open deck
EAC Yes
KC Yes

Digital outputs

Execution FET plus switching
Nominal voltage 24 VDC
Switching voltage 24 VDC -15% / +20%
Output rated current 0.5A
Total rated current 6 A
Connection technology 1-wire technology
Output circuit Source
Output protection Thermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current")
Internal freewheeling diode for switching ind. Loads (see section “Switching inductive loads”)
Diagnostic status Output monitoring with delay 10 ms
Leakage current when output is switched off 5 µA
RDS(on) 210 mΩ
Short-circuit peak current <12 A
Switch-on during overload shutdown or short-circuit shutdown approx.10 ms (depending on the module temperature)
Switching delay
0 → 1 <300 µs
1 → 0 <300 µs
Switching frequency
resistive load max. 500Hz
inductive load See section "Switching inductive loads"
Brake voltage when switching off inductive loads typ. 50VDC
Isolation voltage between channel and bus 500 Vrms

Electrical properties

Potential separation Channel to bus separated
Channel to channel and I/O supply not separated

Using conditions

Installation position
horizontal Yes
vertical Yes
Installation altitude above sea level (sea level)
0 to 2000 m No restriction
>2000 m Reduction of the ambient temperature by 0.5°C per 100 m
Protection class according to EN 60529 IP20

Ambient Conditions

Temperature
Operation
horizontal installation position -25 to 60°C
vertical installation position -25 to 50°C
Derating See section "Derating"
Storage -40 to 85°C
Transportation -40 to 85°C
Humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transportation 5 to 95%, non-condensing

Mechanical properties

Note Order field terminal 1x X20TB12 separately
Order bus module 1x X20BM11 separately
Grid dimension 12.5 +0.2mm