X20AO4622 - Analog output module

X20AO4622 - Analog output module

new in sealed original packaging
Normal price 3 069 kr
/
  • plus taxes + shipping

This site is protected by hCaptcha and the hCaptcha Privacy Policy and Terms of Service apply.

  • Fast delivery
  • New & Sealed Original Items
  • Manufacturer's warranty on all parts
  • Access to stock items available worldwide
  • Feedback within 24 hours
  • Low stock - 8 items left
  • Inventory on the way
  • American Express
  • Apple Pay
  • Google Pay
  • Klarna
  • Maestro
  • Mastercard
  • PayPal
  • SOFORT
  • Union Pay
  • Visa

Do you need more than what we have in stock? Just ask us.

DESCRIPTION:

  • 4 analog outputs
  • Current or voltage signal available
  • 13 bit digital converter resolution
X20 Analog output module, 4 outputs, ±10 V or 0 to 20 mA / 4 to 20 mA, 13 bit converter resolution

Short description

I/O module 4 analog outputs ±10 V or 0 to 20 mA / 4 to 20 mA 

General

B&R ID code 0x1BA3
Status displays I/O function per channel, operating status, module status
Diagnosis
Module Run/Error Yes, via status LED and SW status
Channel type Yes, via SW status
Power consumption
Bus 0.01W
I/O internal 1.8 W (Rev. ≥J0); 2.2W (Rev.
Additional power loss due to actuators (resistive) [W] -
Approvals
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial Control Equipment
HazLoc cCSAus 244665
Process Control Equipment
for Hazardous Locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B(0 to 55 °C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck)
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55 °C
Vibration: 4 g
EMC: Bridge and open deck
EAC Yes
KC Yes

Analog outputs

Output ±10 V or 0 to 20 mA/ 4 to 20 mA, via different terminal points 
max. Output current 10 mA at voltage >5 V
15 mA at voltage <5 V
Digital converter resolution
Voltage ±12 bits
Current 12 bits
Conversion time 300 μs for all outputs
Settling time for output change over full range 500 µs
Switch on/off behavior Internal enable relay for startup
max.Error
Voltage
Gain 0.08%
Offset 0.05% 
Current
Gain 0.09%
Offset 0.05% 
Output protection Short-circuit proof
Output format
Voltage INT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV
Current INT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
Load per channel
Voltage max. ±10 mA, load ≥1 kΩ
Current Load max. 600 Ω (Rev. ≥ J0); 500 Ω (Rev. < J0)
short-circuit proof Current limitation ±40 mA
Output filter Low pass 1st order / corner frequency 10 kHz
max. Gain drift
Voltage 0.015%/°C 
Current 0.02%/°C 
max. Offset drift
Voltage 0.032%/°C 
Current 0.032%/°C 
Error due to load change
Voltage max. 0.11%, from 10 MΩ → 1 kΩ, ohmic
Current max. 0.5%, from 1 Ω → 600 Ω, ohmic
Nonlinearity <0.007% 
Isolation voltage between channel and bus 500 Vrms

Electrical properties

Potential separation Channel to bus disconnected
Channel to channel not disconnected

Using conditions

Installation position
horizontal Yes
vertical Yes
Installation altitude above sea level (sea level)
0 to 2000 m No restriction
>2000 m Reduction of the ambient temperature by 0.5°C per 100 m
Protection class according to EN 60529 IP20

Ambient Conditions

Temperature
Operation
horizontal installation position -25 to 60°C (Rev. ≥ J0); 0 to 55°C (Rev. < J0)
vertical installation position -25 to 50°C (Rev. ≥ J0); 0 to 50°C (Rev.
Derating See section "Derating"
Storage -40 to 85°C
Transportation -40 to 85°C
Humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transportation 5 to 95%, non-condensing

Mechanical properties

Note Order field terminal 1x X20TB12 separately
Order bus module 1x X20BM11 separately
Grid size 12.5 +0.2mm
This area currently has no content. Add content to this area using the sidebar.

You might also be interested in