DESCRIPTION:
- The bus module is the basis for all X20 24 VDC I/O modules
- The internal I/O supply is connected through
- Manual node number assignment
- Independent of the electronic module
- Manual and automatic addressing can be mixed as desired
The BM15 bus module serves as the basis for all X20 24 VDC I/O modules. In addition, a unique address is set with this bus module using a node number switch.
Short description
Bus module | Bus module, with node number switch, 24 VDC coded, internal I/O supply connected through |
General
Power consumption | |
Bus | 0.13W |
I/O internal | - |
Additional power loss due to actuators (resistive) [W] | - |
Approvals | |
CE | Yes |
UKCA | Yes |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user manual) FTZÚ 09 ATEX 0083X |
UL | cULus E115267 Industrial Control Equipment |
HazLoc | cCSAus 244665 Process Control Equipment for Hazardous Locations Class I, Division 2, Groups ABCD, T5 |
DNV | Temperature: B(0 - 55 °C) Humidity: B(up to 100%) Vibration: B(4 g) EMC: B(bridge and open deck) |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV |
EC33B Temperature: 5 - 55 °C Vibration: 4 g EMC: Bridge and open deck |
EAC | Yes |
KC | Yes |
I/O supply
Nominal voltage | 24 VDC |
Permissible contact load | 10A |
Using conditions
Installation position | |
horizontal | Yes |
vertical | Yes |
Installation altitude above sea level (sea level) | |
0 to 2000 m | No restriction |
>2000 m | Reduction of the ambient temperature by 0.5°C per 100 m |
Protection class according to EN 60529 | IP20 |
Ambient Conditions
Temperature | |
Operation | |
horizontal installation position | -25 to 60°C |
vertical installation position | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transportation | -40 to 85°C |
Humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transportation | 5 to 95%, non-condensing |
Mechanical properties
Grid dimension | 12.5 +0.2mm |